DPS Pressure Transducer: precise measurement of differential, positive and negative pressure in non-aggressive gases. Built around a proven inductive measurement system with individual temperature compensation, the DPS delivers excellent long-term stability and an interference-free analogue output over long cable runs. Ideal for cleanroom and critical environment control, medical technology, HVAC, filter monitoring and flow rate measurement.
Measurement Ranges: 0.1 hPa to 1000 hPa, over-, negative- and differential pressure
Output Signal: 0–20 mA, 4–20 mA, 0–10 V, ±5 V or two-wire; square root output optional
Accuracy: 1% FS standard; 0.5% FS (≥ 1 hPa) or 0.2% FS (≥ 2.5 hPa) optional
Electrical Connections: M12 x 1.5 mm cable glands
Process Connections: Ø 6 mm barbs for flexible tube
Media Compatibility: Non-aggressive gases; medium-affected parts Ni, Al, CuBe, PU
Special Features: Damping, limit contacts, LC display, automatic zero adjustment, high overload protection to 2 bar
The DPS measures over-pressure, negative pressure and differential pressure across selectable nominal ranges of 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 1.0, 1.6, 2.5, 4.0, 5.0, 6.0, 10, 16, 20, 25, 50, 100, 160, 200, 250, 400, 500, 600 and 1000 hPa, with further ranges available on request. Standard overall accuracy is 1% FS, improving to 0.5% FS on ranges of 1 hPa and above, or 0.2% FS on ranges of 2.5 hPa and above — figures that include linearity, hysteresis and repeatability error following zero-point calibration and amplitude adjustment. Long-term stability is ≤ 0.5% FS per year and temperature drift ≤ 0.03% FS/K.
Output is selectable between 0–20 mA and 4–20 mA (load ≤ 500 Ω), 0–10 V and ±5 V (load ≥ 2 kΩ), or two-wire. Standard supply is 19–35 VDC, with 230 VAC, 115 VAC, 24 VAC and 12–32 VDC (two-wire only) options; supply influence is under 0.05% and an interference filter is available for noisy power grids. Typical consumption is 10 mA without load, the time constant is 120 ms, and reverse polarity protection is fitted as standard.
Overload capability is fivefold on ranges below 400 hPa and twofold above 400 hPa, with high overload protection to 2 bar available as an option. Sensor capacity is approximately 3 ml. The ABS housing is rated IP54, protection class II, weighs a maximum of 400 g and takes M12 x 1.5 mm cable glands with Ø 6 mm pressure connections for flexible tubing. Standard housing is 120 x 80 x 55 mm; larger enclosures (120 x 80 x 70, 120 x 80 x 85, 122 x 120 x 75 and 122 x 120 x 105 mm) are used where limit contacts, an LC display or automatic zero adjustment are specified. Operating temperature is 10–50 °C as standard, extendable to -10–60 °C, with humidity below 80% RH non-condensing.
Options include damping for strongly fluctuating pressures, one or two limit contacts with 6 A / 230 VAC relay changeover output, a square root output signal for flow applications, a 3.5-digit LC display and automatic zero adjustment at regular intervals. The DPS is CE marked to the Low Voltage Directive 2014/35/EU, EMC Directive 2014/30/EU and RoHS Directive 2011/65/EU.
In critical environment control — cleanrooms, isolation suites, laboratories and containment facilities — the DPS monitors the small room-to-room pressure differentials that maintain containment integrity. Ranges down to 0.1 hPa with 0.2% FS accuracy and automatic zero adjustment make it suitable for long-term unattended monitoring where drift would otherwise compromise the reading.
For medical technology, the inductive measurement principle and individual temperature compensation of each sensor deliver the repeatability required in respiratory, sterilisation and gas-handling equipment. The interference-free analogue output supports reliable transmission back to central control systems over extended cable runs.
Across HVAC and filter technology, the DPS tracks pressure drop across filters, coils and dampers to trigger changeover or maintenance. Limit contacts with relay outputs allow standalone alarm and switching duty without a controller, while the LC display provides local indication at the plant.
For flow rate measurement, the optional square root output signal linearises differential pressure across an orifice plate or venturi directly at the transducer, giving a flow-proportional 0–10 V or 0(4)–20 mA signal without additional processing.