Home / Instrumentation / Environmental, Weather & Climate Products / Feel FHT Humidity & Temperature Transmitter
The Feel FHT is a humidity and temperature transmitter for rooms and air ducts, accurate to ±2 % rH and ±0.3 K. Output relative humidity, absolute humidity or enthalpy alongside temperature, and set it up on site to suit your building management system.
Humidity and temperature have a direct effect on comfort, product quality and energy use. The Feel FHT gives building automation, cleanroom and storage systems a reliable, accurate reading of both, from a single compact transmitter that installs in minutes.
The FHT is not limited to relative humidity. Switch the humidity output to relative humidity (0…100 % rH), absolute humidity (0…150 g/m³) or enthalpy (−50…400 kJ/kg), depending on what your control strategy needs. Enthalpy output is particularly useful for free-cooling and heat-recovery control in air handling units.
A sensitive sensing element and high-resolution electronics deliver ±2 % rH between 10 and 90 % rH, and ±0.3 K between 0 and 50 °C. Drift is low, at ±0.5 % rH and ±0.05 K per year, so the readings your BMS relies on stay trustworthy between service visits. Temperature ranges of −40…80 °C, −20…60 °C or 0…50 °C can be selected, displayed in °C, °F or K.
Choose the room version with a 50 mm sensor tube for wall mounting in the space being monitored, or the duct version with a 200 mm sensor tube for measurement directly in the air stream. The sensor is protected by a 30 µm wire-mesh filter as standard, with a 10 µm sintered filter available for dusty environments.
An optional high-resolution 2.8″ colour TFT display shows humidity and temperature at the device, which makes commissioning and routine checks quick. Measuring range, output signal and time constant are set on site with DIP switches on the board or the configuration software, and sub-ranges can be defined anywhere within the basic measuring range.
Two optional open-collector switching outputs can trigger alarms, fans or dehumidifiers directly when humidity or temperature passes a set point.
Analogue outputs of 0–10 V, 2–10 V, 4–20 mA or 0–20 mA are available as standard. For digital integration into your building management system, choose the RS485 Modbus interface.
Building automation and HVAC control, air ducts and ventilation systems, cleanrooms, greenhouses, storerooms and warehouses, incubators and air cleaners.
Every Feel FHT is supplied with its snap-in mounting frame and all fixing accessories, ready to install. Developed and built in Germany, it shares its housing and mounting system with the rest of the Feel family, including the Feel FC CO₂ transmitter and the Feel FV VOC transmitter. Contact our engineers to choose the right version for your application.