Differential Pressure Transmitters for Cleanroom Pressure Monitoring
A cleanroom suite is only as clean as its pressure cascade. Air should always move from the cleanest zone outwards, through change rooms and airlocks to the corridor, and the differences that make this happen are tiny: typically 10 to 15 Pa between adjacent rooms. A door left open, a loading filter or a fan that drifts off its setpoint can collapse that margin in seconds, so the room-to-room differentials need to be measured continuously, alarmed locally and passed to the building management system with a record that stands up at audit.
Stork Solutions supplies the measurement chain for this work, alongside our wider cleanroom and building automation range: low-range differential air pressure transmitters with spans from 10 Pa, a multi-parameter room sensor, differential pressure transmitters and switches for air handling plant, door-side meters with alarm relays, and a multi-channel data logger that feeds the BMS over Modbus and keeps a traceable history of every room.
Product Spotlight for Cleanroom Pressure Monitoring
Why Cleanroom Pressure Monitoring Matters
Cleanroom standards such as ISO 14644 and EU GMP Annex 1 expect controlled zones to be protected by a defined pressure cascade. Measuring each room-to-room differential continuously, rather than reading a gauge on a walk round, allows facilities and validation teams to:
Hold the cascade between rooms — low-range transmitters resolve the few pascals that separate a grade of cleanliness from the room next door, so a shrinking margin is seen long before the airflow reverses
Separate door events from real faults — signal damping and threshold relays, combined with alarm logic in the BMS or logger, help distinguish a brief dip during a door opening from a sustained loss of pressure
Protect operating theatres and isolator suites — positive rooms keep contamination out, negative rooms keep hazards in, and both depend on the direction of the differential as much as its size
Give the BMS reliable data — 4…20 mA and RS485 Modbus signals let the building management system trend every room, adjust supply and extract fans and escalate alarms to the right people
Keep records for validation and audit — logged, time-stamped pressure history shows that each room stayed within its limits between qualifications, and pinpoints when and where an excursion happened
Differential Pressure Instruments for Every Cleanroom Pressure Monitoring Application
Low-Range Transmitters for Room-to-Room Cascades
Each door in the cascade needs its own differential measurement, with one port referenced to the cleaner room and the other to the room it opens into. For differentials of 10 to 15 Pa, choose a span close to the setpoint so that a loss of a few pascals is a meaningful share of the signal.
Differential Pressure Transmitter DPS
Ranges from 0…0.1 hPa (10 Pa) up to 0…1000 hPa, measuring over-pressure, negative pressure and differential pressure in non-aggressive gases. Accuracy is 1% FS as standard, with 0.5% FS (ranges from 1 hPa) and 0.2% FS (ranges from 2.5 hPa) options. Outputs include 0/4…20 mA, 0…10 V, ±5 V and two-wire, with optional 3.5-digit LC display, damping, automatic zero adjustment and one or two 6 A changeover limit contacts. Its listed applications include cleanrooms, isolation suites, laboratories and containment facilities.
PrimAtü 10 Low Range Differential Air Pressure Transmitter
A freely selectable unidirectional or bidirectional range up to 1000 hPa, with 1% FS accuracy as standard and 0.5% FS or 0.2% FS (ranges from 10 hPa) options. Outputs are 0…10 V, 0…20 mA or 4…20 mA, with optional RS485 Modbus and LCD display. The IP65 housing mounts on a top-hat rail or wall, and zero offset and span can be corrected at the push of a button. Confirm the lowest span available for your cascade with Stork.
Room Monitoring for Operating Theatres and Isolator Suites
Operating theatres, aseptic suites and rooms housing isolators are usually judged on more than pressure alone. Combining the room differential with temperature and humidity in one wall or duct-mounted unit reduces the number of devices to install, wire and calibrate. For pressure inside an isolator or glovebox itself, confirm suitability with Stork.
FEEL Multi-Parameter Sensor
A modular sensor built around differential pressure, with optional temperature and humidity (±0.3 K and ±2%), CO₂ and VOC measurement. Pressure ranges default to 1, 10, 100 or 1000 hPa and can be set to 25, 50, 75 or 100% of the ordered range. It offers a switchable analogue output, optional open collector switch output, optional RS485 Modbus, an optional TFT display and an optional auto-zero function using an internal solenoid. Building automation and cleanroom monitoring are among its listed applications.
Filter and Fan Monitoring in the Air Handling Plant
Most cascade failures start in the plant room rather than the cleanroom. As filters load, supply air falls and room differentials shrink, so monitoring pressure drop across filters and fans gives maintenance teams warning before the rooms themselves go into alarm.
DMD 341 Differential Pressure Transmitter for Gases and Compressed Air
Ranges from 0…6 mbar to 0…1000 mbar with a 2-wire 4…20 mA or 3-wire 0…20 mA or 0…10 V output. A piezoresistive silicon sensor in a compact aluminium housing suits non-aggressive gases, and HVAC pressure monitoring across filters, fans and ducts is a listed application.
DS 233 Differential Pressure Switch for Gases and Compressed Air
The same 0…6 mbar to 0…1000 mbar ranges with one or two PNP switching contacts alongside a 4…20 mA or 0…10 V analogue output. The rotatable 4-digit LED display shows the reading at the unit, and the switch can alert the BMS when a filter or fan differential leaves its set band.
Door-Side Alarms, BMS Integration and Audit Records
Staff need to see a room’s status before they open the door, the BMS needs a clean signal to act on, and the quality team needs a record of every excursion. Local meters with relays handle the first, while a multi-channel logger brings many rooms together for the BMS and for audit.
SRL-49 Process Meter with Bargraph
Accepts 0/4…20 mA, 0/1…5 V and 0/2…10 V inputs and shows them on a 4-digit red LED display with a 20-point red-green bargraph. Up to four relay or open collector outputs switch on one or two thresholds, with an optional analogue output, RS-485 Modbus RTU and a 24 V DC supply for the transmitter. Panel mounted with an IP65 front.
PUR-W410 Large-Size Universal Meter
A wall-mounted meter with 100 mm red LED digits and eight brightness levels, readable from across a corridor or plant room. It accepts 0/4…20 mA and 0…10 V signals among other inputs, with two or four relay or open collector outputs, an optional analogue output and RS-485 Modbus RTU. The enclosure is rated IP30, so confirm suitability for your location with Stork.
CMC-141 Multicon Multi Channel Data Logger & Controller
Up to 72 inputs across 27 input and output card types, with RS485 Modbus as standard and Modbus TCP/IP over Ethernet through the communications module. With the logging licence it records 1 to 60 channels at rates from 0.1 s into 1.5 GB of internal memory, and the notifications licence adds email alerts with channel data and an optional .csv attachment. The built-in web server, USB export and DAQ Manager software with PDF reporting support review and record keeping.
Certifications & Compliance
Approvals and protection ratings vary by model and version, so confirm the options you need on the relevant product page or with our team. The products above offer the following:
CE marking — the DPS is CE marked to the Low Voltage Directive 2014/35/EU, EMC Directive 2014/30/EU and RoHS Directive 2011/65/EU
IP65 — the PrimAtü 10 housing and the SRL-49 front panel
IP54 — the DPS ABS housing, with protection class II
IP30 — the PUR-W410 wall-mounted enclosure
RS485 Modbus communication — standard on the SRL-49, PUR-W410 and CMC-141, and optional on the PrimAtü 10 and FEEL Multi-Parameter Sensor, for direct connection to the BMS